Victron Quattro 12/5000/220 Inverter/Charger

Three phase capability

The Quattro is a very powerful battery charger. It will therefore draw a lot of current from the generator or shore side supply (16A per 5kVA Quattro at 230VAC). A current limit can be set on each AC input. The Quattro will then take account of other AC loads and use whatever is spare for charging, thus preventing the generator or mains supply from being overloaded.

pdf
Specs sheet

Order Code:QUATTRO 12/5000/220

Description

Two AC inputs with integrated transfer switch
The Quattro can be connected to two independent AC sources, for example shore-side power and a generator, or two generators. The Quattro will automatically connect to the active source.

Two AC Outputs
The main output has no-break functionality. In the event of a grid failure, or shore or generator power being disconnected, the Quattro takes over the supply to the connected loads. This happens so fast (less than 20 milliseconds) that computers and other electronic equipment will continue to operate without disruption. The second output is live only when AC is available on one of the inputs of the Quattro. Loads that should not discharge the battery, such as air-conditioning or a water heater can be connected to this output.

Unique PowerAssist feature
The Quattro will prevent overload of a limited AC source. First, battery charging will automatically be reduced when otherwise an overload would occur. The second level will boost the output of a generator or shore side supply with power taken from the battery.

Virtually unlimited power thanks to parallel operation
Up to 6 Quattros can operate in parallel to achieve higher power output. Three phase or split phase operation is also possible.

Features

  • Two AC Outputs
  • Virtually unlimited power thanks to parallel operation
  • Three phase capability
  • PowerControl – Dealing with limited generator, shore side or grid power
  • PowerAssist – Boosting the capacity of shore or generator power
  • Solar energy: AC power available even during a grid failure
  • System configuring
  • On-site Monitoring and control
  • Remote Monitoring and control
  • Remote configuring

Technical Data

12/5000/220-100/100
PowerControl / PowerAssist Yes
Integrated Transfer switch Yes
AC inputs (2x) Input voltage range: 187-265 VAC Input frequency: 45 – 65 Hz Power factor: 16163016 or 50
Maximum feed through current (A) 2×100
Input voltage range (V DC) 9,5 – 17V 19 – 33V 38 – 66V
Output (1) Output voltage: 230 VAC ± 2% Frequency: 50 Hz ± 0,1%1200160020003000