MultiPlus II (formerly called MultiGrid-II)

The MultiPlus can be used in off-grid as well as grid-connected PV and other alternative energy systems

pdf
Spec Sheet
pdf
Comparsion Sheet

Description

The MultiPlus-II combines the functions of the MultiPlus and the MultiGrid. It has all the features of the MultiPlus, plus an external current sensor option which extends the PowerControl and PowerAssist function to 35A. It also has all the features of the MultiGrid with built-in anti-islanding and an increasingly long list of country approvals.

Features

A MultiPlus, plus ESS (Energy Storage System) functionality

The MultiPlus-II combines the functions of the MultiPlus and the MultiGrid. It has all the features of the MultiPlus, plus an external current sensor option which extends the PowerControl and PowerAssist function to 35A. It also has all the features of the MultiGrid with built-in anti-islanding and an increasingly long list of country approvals.

PowerControl and PowerAssist – Boosting the capacity of grid or generator power

A maximum generator or grid current can be set. The Multi will then take account of other AC loads and use whatever is extra for battery charging, thus preventing the generator or grid from being overloaded (PowerControl function). PowerAssist takes the principle of PowerControl to a further dimension. Where peak power is so often required only for a limited period, the Multi will compensate insufficient generator, shore or grid power with power from the battery. When the load reduces, the spare power is used to recharge the battery.

ESS: Energy Storage Systems

The MultiPlus can be used in off-grid as well as grid-connected PV and other alternative energy systems. Several system configurations are possible, for more detailed information see the ESS Design and configuration manual.

On-site monitoring and control

Several options are available: Battery Monitor, Digital Multi Control Panel, Color Control Panel, Bluetooth (Venus GX or Color Control panel needed),
laptop or computer.

Remote configuring and monitoring

Install a Venus GX or a Color Control Panel to connect to the internet. Data can be stored and displayed on our VRM (Victron Remote Management) website, free of charge.
When connected to the Ethernet, systems can be accessed remotely and settings can be changed.

Technical Data

MultiPlus-II 48/3000/35
Transfer switch 32A
Maximum AC input current 32A
INVERTER
DC Input voltage range 38 – 66 V
Output Output voltage: 230 VAC ± 2%
Frequency: 50 Hz ± 0,1% (1)
Cont. output power at 25°C (3) 3000 VA
Cont. output power at 25°C 2400 W
Cont. output power at 40°C 2200 W
Cont. output power at 65°C 1700 W
Peak power 5500 W
Maximum efficiency 95 %

Accessories

Current Transformer for MultiPlus-II

Current Transformer 100A:50mA for MultiPlus-II – CTR110000500